FirstLine P 924
FirstLine® P 924 Emergency Lighting System (ELS) delivers high performance, tailored to meet the demands of emergency lighting applications. With a cost-effective reliable design, the FirstLine® P 924 helps to ensure personnel safety, during an outage condition.
Contact Us about FirstLine P 924
The FirstLine® P 924 offers more security and versatility to meet illumination requirements, and is the perfect complement for all lighting applications. Our inverter technology effectively maintains critical equipment with extended brownout protection, tight voltage regulation, and power conditioning. Tight voltage regulation assures that facility egress lumens are maintained 100% at emergency lighting fixtures, in all modes of operation, and also extends ballast, LED driver, and lamp life.
FirstLine® P 924 features unparalleled quality and reliability, with constant conditioned power to virtually any lighting type. The Staco optional Power Distribution Unit (PDU) makes for a well-coordinated circuit distribution system. VRLA and Lithium Ion Battery Solutions.
Power Rating (kW) | 58.5, 72, 90, 112.5, 144, 180, 210, 225 |
Battery | 90 Minutes, VRLA Maintenance Free Cell. Ask about Lithium Ion Battery Solutions (Modified battery times can be provided under Category “OUST”) |
Nominal voltage | 480Vac 3-phase (with or without neutral) |
Nominal voltage tolerance | ± 15% (can be regulated from ± 10% to ± 25% from the control panel) |
Nominal frequency | 60 Hz |
Frequency tolerance | ± 2% (can be regulated up to ± 6% from the control panel) |
Environmental:
Ambient temperature | 0° C to 40° C |
Storage temperature | -25° C to 70° C |
Relative humidity | 20 – 90% non-condensing |
Altitude | 3,281 feet without derating |
Audible noise | 65 dBA @ 1 meter 68 dBA @ 1 meter |
Input:
Nominal voltage | 480Vac 3 phase, 3 or 4-Wire + Grd. (208V with Transformer) |
Nominal voltage range without battery contribution | -10%, +15% |
Voltage range in battery mode | -40%, + 15% |
Input frequency range | From 45 to 65Hz |
Power factor at nominal voltage (480 V) and battery charged from 25% to 100% of the load | >0.99 |
Current Harmonic distortion (THDi) (with mains distortion <2%) • load 100% • load 75% • load 25÷50% | ≤ 3% ≤ 5% ≤ 8% |
Progressive rectifier (Walk-in) | from 0 to 30 seconds (configurable) |
Delay of Progressive start of rectifier (Power Walk-in delay timer) | from 0 to 120 seconds (configurable) |
Nominal current absorbed (480V):
58.5:
78
144:
188
72:
96
180:
235
90:
120
210:
294
112.5:
150
225:
294
Maximum current absorbed at full load and battery recharging (Amps):
58.5:
89
144:
212
72:
109
180:
265
90:
136
210:
331
112.5:
160
225:
331
Inverter:
Static variation | ± 1% |
Dynamic variation | ± 5% |
Crest Factor | 3:1 |
Voltage distortion with linear load | 1% (typical), 2% (max) |
Voltage distortion with non-linear load | < 3% |
Frequency stability with synchronized inverter to the by-pass network. | ± 2% ( ± 1% to ± 6% from control panel) |
Frequency stability with not synchronized inverter to the by-pass line | ± 0.05% |
Speed of frequency variation | 1Hz/sec (parallel units can be calibrated from 0.1 to 1Hz/s) |
Phase voltage asymmetry with balanced and unbalanced load. | ≤ 1% |
Phase displacement of the voltages with balanced and unbalanced loads. | 120 ± 1 °el |
Overload in referred to the nominal power • Three phase • Single phase | 110% for 60 minutes, 125% for 10 minutes, 150% for 1 minute 200% for 7 seconds |
Inverter efficiency | 95% |
1. Due to continuous product improvements, program specifications are subject to change without notice.